OVERVIEW: Sulphuric Acid caused deterioration of the existing fiberglass matting. The failure of the previous fiberglass lining had enabled permeation, allowing serious corrosion of the concrete slab. The Chem-tect™ system has provided years of maintenance-free service and excellent chemical resistance since recoating.
INDUSTRY
ENVIRONMENT
Sulphuric Acid has caused deterioration of the existing fiberglass matting. The failure of the previous fiberglass lining had enabled permeation, allowing serious corrosion of the concrete slab
SUBSTRATE
Concrete
CHALLENGE
A core drilling process and testing procedure was undertaken to analyse the extent of the Ammonia Sulphate ingress before planning a work method to avoid contamination from other work happening on site
SOLUTION
Chem-tect™ Vinyl Ester system is filled with screened glassflake technology for long lasting protection from aggressive chemicals such as sulphuric acid, abrasion and high temperature environments
SCOPE
The lining was cut and removed by sections to allow the plant to continue operations
The required surface preparation was undertaken to remove laitance from the concrete surface
Where repairs to the concrete were needed, the area was broken up with a Jackhammer
Crushed rock was placed in void and compactor was used to level fill
Steel Reinforcement was placed
Treatment with Vinyl Ester Primer to seal the porous surface
Core drilling samples taken to assess extent of concrete damage
Pour fast setting Polymer Concrete into position with an air powered hammer chisel to stabilize the ground
Trowel off and cure
Promote second coat on site for fast reaction
Top with Garnet to provide anti slip properties
OUTCOME
Chemco International’s Chem-tect™ system has provided years of maintenance-free service and excellent chemical resistance. These materials are substantially stronger than the original slab and will protect the slab in the future against mechanical damage and further sulphuric acid ingress
RELATED CASE STUDIES
22 year old pipes coated with glass flake vinyl ester
Internal lining in excellent condition Abrasive blast externals Recoating of externals Recoating of externals in basement OVERVIEW: The pipes were originally coated internally using
Premature Failure of 316L Stainless Steel Pipes
Severe pitting after 2 months in service After abrasive blasting Damaged internals rebuilt and coated Externally applied caution OVERVIEW: New 316L pipe failed after
Corrosion protection ensures a long life for a new 98% Sulphuric Acid Bund
Newly constructed bund Primer application Application of final coat Job completed OVERVIEW: Chemcote was contracted to apply acid protection to a newly constructed delivery